Overview

Product

Elexant 4010i Heat Trace Controller

Raychem Elexant 4010i Series is a range of compact, full-featured, touch screen based, single-point heat-tracing controllers, with ground fault protection. It provides control and monitoring for both freeze protection and process temperature maintenance. Available with either an electromechanical relay (EMR) for use in non hazardous areas, or solid-state relay (SSR) for use in non hazardous and Class I Div. 2 / Zone 2 hazardous locations. Capable of controlling up to 32A at 277 Vac.

Details

Features

  • Global approvals for CID2/Zone 2, ATEX Zone 2, IEC Ex Zone 2
  • Ready to install: no need for custom panel design or field assembly
  • Flexible control options: up to three directly- connected temperature sensors; also supports 4-20 mA inputs, allowing the use of external temperature sensor converters with thermocouples or other sensor types; also line sensing, ambient sensing, proportional ambient sensing control (PASC) and power limiting modes.
  • Flexible monitoring options: ground fault, temperature, current and voltage to ensure system integrity
  • Multiple communication ports: RS485 and Ethernet, readily connected to a distributed control system (DCS); support both the Modbus RTU and Modbus/TCP protocols; can network to a host PC running Windows®-based Raychem Supervisor software for central programming, status review, and alarm annunciation
  • Reliable during long life: 10 year product warranty available

Specifications

Autocycle: 1 - 750 h
Communication: RS-485
Communication Protocol: Modbus/TCP
Control Algorithms: On/Off, PASC, Always On, Always Off
Control Max Current: 32A @ 40°C, De-Rated to 24A @ 50°C and Further De-Rated to 16A @ 60°C
Control Max Voltage: 277 VAC Nominal, 50/60Hz
Control Relay Type: Double-Pole, Mechanical
Current Alarm: 0.1 A
Ethernet: 10/100 Base-T
Ground Fault Alarm: 10 - 500 mA
Max Ground Terminal Wire Size: 33 mm²
Max Heating Cable Output Wire Size: 16.8 mm²
Max Power Supply Input Wire Size: 16.8 mm²
NEMA Rating: 4X
Operating Temperature: -40 - 140 °F
Relative Humidity: 0% to 90%, Noncondensating
RS-485 Cable Type: One 2-Wire, Shielded Twisted Pair
Temperature Alarm: -328 - 1292 °F
Temperature Control Range: -328 - 1292 °F
Voltage Alarm: 80 V

Product Items

Header 1
Header 2
Header 3
Header 4
Header 5
Header 6
Header 7
Header 8

Video